1-866-494-4610

Dwyer LPI-111 Process Loop Powered Indicator 4-20Ma Input

Dwyer LPI-111 Process Loop Powered Indicator 4-20Ma Input
Images for general purposes only. Actual may be different than depicted.
Dwyer LPI-111 Process Loop Powered Indicator 4-20Ma Input

Dwyer LPI-111 Process Loop Powered Indicator 4-20Ma Input

SKU: LPI-111
Rating:
* This Product is Now Obsolete
No Replacement Available
0
0
0
0
0
LPI-111

The micro-pressure based Model LPI Loop Powered Indicator accepts a 4-20 mA input signal and displays the associated process variable such as pressure, level, flow, temperature or relative humidity. Local or remote indication of process variable can be viewed on the bright red four-digit LED. The user can quickly modify the instrument configuration via three push buttons. Program input/output scaling, engineering units, offset, decimal point position, and password protection. The Series LPI contains several linearizations which can be applied to the display including straight linear, square root, x 3/2, x 5/2, or a user defined 19 segment linearization curve. The indicator is housed in a NEMA 4X (IP65) polycarbonate enclosure with a 1/2" female NPT side port.

Input 4 to 20 mA
Maximum Input Current 100 mA for 1 minute
Power Requirement 2-wire 4-20 mA loop powered
Ambient Operating Temperature -4 to 167F ( -20 to 75C )
Front Panel Protection NEMA 4x ( IP65)

Download Product Information:

Installation Manual

Catalog Page

Q & A: Ask the Questions, share answers

Do you have questions about this product?


Q: 
What is the voltage level that can be used to power this sensor, 12/24v dc ?
Asked on Jul 04, 2019 by PRAVEEN from Ontario,Canada
1 Answers

Have an answer? Click Here

A: 
The Dwyer LPI-111 Process Loop Powered Indicator accepts a 4-20 mA input signal.  The maximum current rating for this device is 100 mA for 1 minute. Exceeding this value will destroy the device. Fuse protection of the current loop to which this device is connected is highly recommended. This unit must only be series connected to 4 to 20 mA current loop. This device will be destroyed if connected directly across any supply with a current output greater than 100 mA. The power requirments is 2-wire 4-20 mA loop powered.
Replied on Jul 04, 2019 by Ori from Industrial Stores