DIAGNOSTIC INDICATOR | |
LED | DESCRIPTION |
ON | Control Fault |
1 Flash | Air Flow Fault |
2 Flashes | Flame No Call for Heat |
3 Flashes | Ignition Lockout |
Local Spark Rate | 25/30 sparks/sec |
---|---|
Remote Spark Rate | 50/60 sparks/sec |
Type of Gas | Natural, LP, or manufactured |
Flame Failure Response | 0.8 Seconds Maximum |
Flame Sensitivity | 0.7 µA Minimum |
Tries for Ignition | 3 Tries |
Ignition | 15 Seconds |
Pre-Purge | 45 Seconds |
Interpurge | 45 Seconds |
Input | 24 VAC, 50/60 HZ, 300 MA |